AutoAdapt Modes - Support Status
This document details the support status for AutoAdapt control modes on the Grundfos ALPHA HWR pump.
Overview
AutoAdapt is an intelligent pump control algorithm that automatically adjusts operation based on system characteristics and demand. The GENI protocol defines several AutoAdapt variants:
| Mode ID | Name | ALPHA HWR Support |
|---|---|---|
| 5 | AUTO_ADAPT (generic) | Limited |
| 13 | AUTO_ADAPT_RADIATOR | Full |
| 14 | AUTO_ADAPT_UNDERFLOOR | Full |
| 15 | AUTO_ADAPT_RADIATOR_AND_UNDERFLOOR | Full |
| 26 | PROPORTIONAL_DIFF_PRESSURE | Not Supported |
Mode 5: AUTO_ADAPT (Generic) - Limited Support
Discovery Results
Configuration Data: - SubID 11 found in Object 86 (PumpConfiguration) - Setpoint limits available: min=1.48m, max=1.52m, default=1.50m - Data format: uint16 (Pascals), not float32 like other modes - Very narrow operating range (0.04m spread)
Mode Switching: - Class 3 fallback command 0x06 exists - Mode switch commands succeed but verification shows mode doesn't change reliably - May require specific firmware version or system conditions
Setpoint Writing: - Register IDs unknown - library tries multiple candidates (0x1D, 0x06, 0x05) - Success not guaranteed
Implementation Status
Library Support:
CLI Support:
# Available but displays warning
alpha-hwr control set-autoadapt --value 1.5
# Output:
# Note: Mode 5 (AUTO_ADAPT) has limited support.
# Consider using specific variants (radiator/underfloor/combined) instead.
Recommendations
DO NOT USE Mode 5 for production deployments. Instead, use the specific AutoAdapt variants:
| System Type | Recommended Mode | Command |
|---|---|---|
| Radiator heating | Mode 13 (AUTO_ADAPT_RADIATOR) | set_autoadapt_radiator() |
| Underfloor heating | Mode 14 (AUTO_ADAPT_UNDERFLOOR) | set_autoadapt_underfloor() |
| Combined systems | Mode 15 (AUTO_ADAPT_COMBINED) | set_autoadapt_combined() |
Why Mode 5 Has Limited Support
Possible Reasons:
- Firmware Evolution: Mode 5 may be legacy/deprecated in favor of specific variants (13-15)
- Hardware Limitations: ALPHA HWR may lack sensors/logic for generic AutoAdapt
- Configuration Requirements: May require additional setup not implemented in library
- Narrow Range: 0.04m spread suggests it's a placeholder or diagnostic mode
Mode 26: PROPORTIONAL_DIFF_PRESSURE - NOT Supported
Discovery Results
Configuration Data: - No SubID found in Object 86 (tested 0-65) - No factory configuration available - No setpoint limits defined
Mode Switching: - No Class 3 fallback command - Explicitly returns error: "Unsupported Control Mode for Set: 26"
Conclusion: Mode 26 is NOT implemented in ALPHA HWR firmware.
Implementation Status
Library: Not implemented (no set_proportional_diff_pressure() method)
CLI: Not available
Why Mode 26 Is Not Supported
Analysis:
- Product Line Differentiation: Proportional Differential Pressure may be exclusive to higher-end models (ALPHA3, MAGNA3)
- Sensor Requirements: Requires differential pressure sensors not present in ALPHA HWR
- Application Specific: More relevant for complex hydronic systems than recirculation pumps
Alternative: Use Mode 1 (PROPORTIONAL_PRESSURE) which IS fully supported:
Fully Supported AutoAdapt Modes
Mode 13: AUTO_ADAPT_RADIATOR
Best for: Radiator heating systems with high-temperature operation.
Configuration: - SubID: 19 - Format: uint16 (Pascals) - Typical range: 0.5 - 6.0 m - Setpoint register: 0x1E
Usage:
Mode 14: AUTO_ADAPT_UNDERFLOOR
Best for: Underfloor heating systems with low-temperature operation.
Configuration: - SubID: 21 - Format: uint16 (Pascals) - Typical range: 0.3 - 4.0 m - Setpoint register: 0x1F
Usage:
Mode 15: AUTO_ADAPT_RADIATOR_AND_UNDERFLOOR
Best for: Combined radiator and underfloor heating systems.
Configuration: - SubID: 23 - Format: uint16 (Pascals) - Typical range: 0.4 - 5.0 m - Setpoint register: 0x20
Usage:
Testing Methodology
Hardware Probing
# Probe for configuration SubIDs
python probe_autoadapt_config.py <DEVICE_ADDRESS>
# Test mode switching
python test_mode_support.py <DEVICE_ADDRESS>
# Test Class 3 commands
python test_mode5_class3.py <DEVICE_ADDRESS>
Test Results (ALPHA HWR Family 52, Type 7, Version 2)
| Test | Mode 5 | Mode 26 |
|---|---|---|
| SubID found | Yes (11) | No |
| Limits readable | Yes | No |
| Mode switch | Partial | Fails |
| Setpoint write | Unknown | N/A |
Comparison with Other Modes
| Mode | Name | Support | Typical Use |
|---|---|---|---|
| 0 | CONSTANT_PRESSURE | Full | Fixed differential pressure |
| 1 | PROPORTIONAL_PRESSURE | Full | Flow-dependent pressure |
| 2 | CONSTANT_SPEED | Full | Fixed RPM operation |
| 5 | AUTO_ADAPT | Limited | Generic adaptive (use 13-15 instead) |
| 8 | CONSTANT_FLOW | Full | Fixed flow rate |
| 13 | AUTO_ADAPT_RADIATOR | Full | Radiator systems (RECOMMENDED) |
| 14 | AUTO_ADAPT_UNDERFLOOR | Full | Underfloor heating (RECOMMENDED) |
| 15 | AUTO_ADAPT_COMBINED | Full | Mixed systems (RECOMMENDED) |
| 26 | PROPORTIONAL_DIFF_PRESSURE | None | Not available on ALPHA HWR |