Telemetry & Monitoring

The ALPHA HWR streams real-time operational data (Flow, Head, RPM, Power, Temperature) using Class 10 DataObject notifications.

Unlike traditional Request/Response polling, the pump automatically "pushes" these updates to the client once the connection is established and authenticated. This allows for high-frequency updates (approx. 10Hz) without saturating the BLE bandwidth with read requests.

Notification Mechanism

Telemetry arrives as GENI Response frames on the main characteristic.

  • Frame Start: 0x24 (Response/Notification)
  • Class: 0x0A (Class 10 DataObject)
  • Source: 0x0A (Pump)

Payload Structure

The payload of a telemetry packet identifies what data it contains using a SubID and ObjID.

[Header...] [Class=0x0A] [OpSpec] [SubID (2B)] [ObjID (2B)] [Data Payload...] [CRC]

Telemetry Objects

The library decodes the following specific objects. Note that a single BLE packet usually contains only one of these objects at a time. The client must aggregate them to build a complete state.

1. Motor State (Detailed)

Contains electrical and mechanical performance data.

  • SubID: 0x0045 (69)
  • ObjID: 0x0057 (87)
Offset Type Unit Description
+0 Float32 Volts AC Input Voltage (0 - 300)
+8 Float32 Amps Current Draw (0 - 10)
+16 Float32 Watts DC Power Consumption (0 - 1000)
+20 Float32 RPM Motor Speed (0 - 6000)
+24 Float32 °C Converter Temperature (-20 to 120)

2. Flow & Head

Contains hydraulic performance data.

  • SubID: 0x0122 (290)
  • ObjID: 0x005D (93)

Data Offsets:

Field Passive Stream (+0x0E) Active Query (+0x2B) Type Unit
Flow Rate +0 +24 Float32 \(m^3/h\)
Head Pressure +4 +28 Float32 Meters

Conversion Factors:

  • \(GPM = m^3/h \times 4.4029\)
  • \(Feet = Meters \times 3.2808\)
  • \(PSI = Meters \times 1.422\)

3. Temperatures

Contains thermal sensor readings from various points in the system.

  • SubID: 0x012C (300)
  • ObjID: 0x005D (93)

Data Offsets:

Field Passive Stream (+0x0E) Active Query (+0x14) Type Unit
Media Temp +0 +0 Float32 °C
PCB Temp +4 +4 Float32 °C
Ambient Temp +8 +8 Float32 °C

4. Alarms and Warnings

Contains active alarm and warning codes reported by the pump's diagnostic system.

  • SubID: 0x0000 (0) for Alarms, 0x000B (11) for Warnings
  • ObjID: 0x0058 (88)

Query Method:

Unlike other telemetry that streams automatically, alarms and warnings must be queried explicitly using Class 10 READ operations:

  • Query Alarms: Register 0x580000
  • Query Warnings: Register 0x58000B

Response Format:

The pump responds with OpSpec 0x09 (Active Query Response), containing an array of uint16 alarm/warning codes:

Offset Type Description
+0 uint16[] Array of active alarm/warning codes (big-endian)

Data Interpretation:

  • Each code is a 2-byte unsigned integer in big-endian format
  • A value of 0x0000 means "no active alarms/warnings" (normal state)
  • Non-zero values indicate specific alarm/warning conditions
  • Zero values in the array should be filtered out when parsing
  • The array is typically terminated with a trailing zero

Example Codes:

0x0000 = No alarms/warnings (healthy state)
0x002A = Alarm code 42
0x0007 = Alarm code 7
0x0005 = Warning code 5

Polling Recommendations:

  • Poll every 5-10 seconds for proactive monitoring
  • Poll immediately after mode changes or error indicators
  • Avoid polling faster than 1 second to prevent overwhelming the pump

See Also: Packet Trace: Alarms and Warnings for detailed wire format and examples.

5. Setpoint RPM

Reserved for setpoint notifications (passive stream only, not actively queried).

  • SubID: 0x0001 (1)
  • ObjID: 0x012F (303)

Note: This telemetry object is reserved for potential future use. Currently, RPM setpoints are controlled via Class 10 SET operations rather than passively observed.


Active Polling (Modern Approach)

While the pump supports a high-frequency passive stream, the most reliable way to get a single snapshot of the current state is to use Class 10 INFO Queries.

Modern Snapshot Sequence

  1. Request Motor State: Query Register 0x570045.
  2. Request Flow/Head: Query Register 0x5D0122.
  3. Request Temperatures: Query Register 0x5D012C.

Responses will use the "Active Query Response Layout" described in Wire Format.

Legacy Polling (Class 3)

Older firmware or specific integration scenarios might require active polling instead of passive listening. The device supports Class 3 Register Reads for this purpose.

  • Command: READ (OpCode 0x03)
  • Frame Start: 0x27 (Request)

Key Registers

Register Address Name Data Contained
0x5E0004 ELECTRICAL Voltage (AC/DC), Current, Power, RPM
0x5D0122 EXTENDED_FLOW Flow, Head
0x5D012C TEMPERATURE Media, PCB, Control Box Temps

Note: The library's update_telemetry() method attempts to use Class 10 streams first, but can fallback to Class 3 polling if the stream is undetected.