Bench findings

Measured against an ALPHA HWR (BLE EF159DD1-…, firmware reporting 2026-08-04) rather than inferred from code or captures. Each entry says what was measured and how, so a future disagreement can be settled by repeating the measurement instead of re-reading the source.

The second byte of a response is a length field

Not an operation specifier. Across 13 objects and 10 distinct values the operation bits are always 00, and both of these hold without exception:

len(frame)  == (byte5 & 0x3F) + 8
frame[1]    == (byte5 & 0x3F) + 4

This retired an inherited filter. The set {0x30, 0x2B, 0x14, 0x2E, 0x2D, 0x09}, carried in the code as "register-read operation specifiers", is really the payload sizes 48, 43, 20, 46, 45 and 9 — so it rejected replies by length. That is why the event log, whose entries carry a 20-byte payload, had to be exempted from it by hand.

Replies are identified by a per-object type code

The pump does not echo the Object/Sub it was asked for. It answers with a type code, stable per object, in the identifier fields at bytes 6-9. The measured table lives in protocol/matcher.py::RESPONSE_IDENTIFIERS; range ends were checked rather than extrapolated, which is how the power-on-time trend (53/454) turned out to use a different type from the other three.

Two objects share a type code and differ only in the first field:

Object Identifiers
91/430 temperature range 0x0003, 0xF402
88/10200+ event log entry 0x0000, 0xF402

so the "Sub-ID 0 is a wildcard" rule that used to discard the first field made each a valid answer to the other's read.

Object 86: which sub-id reports what

Sub Role Measured
6 operation request control_source = 0 regardless of state
7 prioritized state control_source = 1 (Local/Panel)
10 mode request reads back operation_mode = NoCmd, set_point = NaN

Sub 7 is the one worth reading. Sub 10 reading back its own no-op sentinels is what confirmed the unfused mode-change payload.

3671.0 is the pump's maximum speed setpoint

Requesting 600 RPM stored 1650; requesting 4400 stored 3671.0. It also appears verbatim in the speed-limits block (86/13), alongside 1650 as the minimum. So the old default suffix 45 65 70 00 was not an arbitrary constant — every start() that fell back to it was commanding maximum speed.

The pump clamps rather than rejecting, which is what makes a clamped verdict meaningful: the write succeeds and stores a different value.

Flow setpoints are SI m³/s; telemetry flow is m³/h

Both are correct, and they are different encodings rather than a mismatch. A setpoint written in m³/h reaches the pump 3600× too large and is rejected as out of range, leaving the stored value untouched — which is why the register looked frozen.

The temperature-range object validates nothing

Measured 2026-08-05, writing through set_temperature_range_control and reading back each time. The pump stored every value offered, including ones no hot-water system could mean:

Asked Stored
20.0 – 25.0 20.0 – 25.0
55.0 – 60.0 55.0 – 60.0
60.0 – 65.0 60.0 – 65.0
62.0 – 70.0 62.0 – 70.0
15.0 – 25.0 15.0 – 25.0
0.0 – 5.0 0.0 – 5.0
−10.0 – 0.0 −10.0 – 0.0
90.0 – 99.0 90.0 – 99.0
100.0 – 120.0 100.0 – 120.0

No clamping, no rejection, no lower or upper bound anywhere in the range tried. This is the opposite of the setpoint objects, which clamp silently (600 RPM → 1650), and it matters for two reasons:

  1. The client's 20–70 °C guard is the only guard there is. It is not a mirror of a firmware limit — nothing on the pump will stop a caller storing −10 °C. Ports that omit their own validation have none.
  2. A clamped result is impossible for this object, so an accepted here really does mean the pump holds what you asked for.

The pump was restored to its original 35.0 / 38.9 / autoadapt-on afterwards.

Setpoint clamping, re-confirmed

Measured again 2026-08-05 through the verified write path, on the same unit:

Asked Status Stored
600 RPM clamped 1650.0
4400 RPM clamped 3671.0
2000 RPM accepted 2000.0

Identical to the first measurement, and identical to the pump's own limits block at Object 86 Sub 13. The schedule was still enabled afterwards, which is the configuration-commit fix holding.

Object 91: Sub 421 holds the live cycle configuration

[flow setpoint f32 m³/s][on minutes][off minutes], measured as 0.227 m³/h, 5, 15. Sub 430 is TemperatureRangeControlUserSettings, whose trailing bytes are the on/off-time limits: measured 0f 3c 02 05 01, not the 00 00 00 16 00 the code used to send as a constant.

A setpoint write while stopped turns the pump on

Measured directly: stopped, wrote a Constant Speed setpoint, pump came on. The control frame fuses the run state with the setpoint, so a write has to carry some run state — which is why it must be resolved from the pump rather than assumed.

The configuration commit carries the schedule's enabled flag

The commit writes the whole ClockProgramOverview. The hardcoded APDU the code used to send had clock_program_enabled = 0x00, so — because a commit follows every setpoint write — changing a setpoint switched a live schedule off. Observed on a real schedule.

The clock program only acts when the pump is AUTO

A stopped pump ignores it: a weekly window opened with the motor at 0 RPM throughout. Combined with the rule that the motor runs only inside a window when the schedule is enabled, STOP + schedule-enabled is a state that can never run.

Disabling the weekly schedule also disables single events — they are part of the same clock program.

Single-event timestamps are local Unix time

Wall-clock fields stamped as though they were UTC (timegm(local fields)), not a true UTC epoch. Measured behaviourally: with the pump AUTO, the schedule enabled and no weekly window competing, an event written under this encoding started the motor 4 seconds after the intended wall clock. The two candidate encodings are a UTC offset apart, so the result is unambiguous.

This cannot be caught by verification: the value round-trips byte-identically either way, so the write settles as accepted and a readback agrees with itself while the event opens hours from where it was meant to.

This pump exposes 5 single-event slots, not 35

ClockProgramOverview byte 1 (max_nof_single_events) reads 0x05, and Object 84 Sub 905 does not answer. The slot count should be taken from the overview rather than assumed.


2026-08-20 session

Measured against the same ALPHA HWR, reported by its own Class 7 strings as product ALPHA HWR, serial 10000479, software 92601618V04.02.01.02539, hardware 92601617V01.03.00.00469, BLE 92811431V06.00.01.00001. Its advertisement reports family 52, type 7, version 2.

The Class 7 header is six bytes, and byte 5 is a byte count

The reply is [STX][LEN][DST][SRC][0x07][Count][...STRING...][CRC16]. The first character is at offset 6, and there is no echoed string ID.

24 0E F8 E7 07 0A 41 4C 50 48 41 20 48 57 52 00 83 8D
                ^^ count = 10        ^^ "ALPHA HWR\0"

Reading from offset 7 dropped the first character of every string. The two most-read strings were patched up afterwards and so looked correct — an "A" prepended to LPHA HWR, and a "1" prepended to a serial reading 0000479. The second was right for this unit only by coincidence; a serial beginning 20 would have been corrupted. The version strings had no such patch and were short. Before and after, on the same pump:

software  2601618V04.02.01.02539  ->  92601618V04.02.01.02539
hardware  2601617V01.03.00.00469  ->  92601617V01.03.00.00469
BLE       2811431V06.00.01.00001  ->  92811431V06.00.01.00001

Class 7 needs no handshake at all

Five string reads answered on a link that had sent no opening packets — connect, subscribe, read. This is the same conclusion connection.md reached from the captures, now confirmed by not sending them.

The type numbers, and a naming trap in this client

Bytes 6-9 of a reply are [00][TypeH][TypeL][Version], so the type spans bytes 7-8 and the version is byte 9. Decoded that way, and confirmed against geni_profile_52_7.xml:

bytes 6-9 type / version profile name
00 01 00 03 256 v3 ProtectedMotorStateDetails
00 02 35 02 565 v2 PumpedMediaRelatedProcessValuesExtended
00 02 16 02 534 v2 MediaTemperatureInfo
00 02 3a 01 570 v1 FaultsByArrayExtended
00 01 2f 01 303 v1 operation status
00 01 2d 01 301 v1 setpoint factory config
00 00 da 01 218 v1 ClockProgramOverview
00 01 42 01 322 v1 DateTimeActual
00 03 f4 02 1012 v2 temperature range config

The trap. This client's type_high and type_low_ver split those same four bytes into two 16-bit halves one byte off the real boundary - a convention inherited from the ESPHome port, which kept it deliberately because comparing both halves is equivalent to comparing type and version together. That is true, and the matcher relies on it. But the names read as though they were the type's own halves, and they are not: "type_low_ver 0x2F01" is not a type, it is the second byte of type 303 and its version.

Quote object_type / object_version in prose, and leave the pair form to the matcher. The table above is the vocabulary the vendor's own profile uses.

A response's bytes 6-9 are [00][TypeH][TypeL][Version]

Measured by reading each object and recording the answer:

read reply bytes 6-9 type
86/7 operation status 00 01 2f 01 303 v1
86/13, 86/15, 86/17, 86/39 00 01 2d 01 301 v1 — all four
84/1 schedule overview 00 00 da 01 218 v1
94/101 clock 00 01 42 01 322 v1
91/430 temperature range 00 03 f4 02 1012 v2
motor state 00 01 00 03 3 v1
flow / head 00 02 35 02 0x3502 v2
temperatures 00 02 16 02 0x1602 v2
88/0 alarms and 88/11 warnings 00 02 3a 01 0x3A01 v2 — both

Two collisions matter. The four setpoint ranges are indistinguishable in a reply, so a chain reading them must be sequential and stop at the first failure. Alarms and warnings are indistinguishable too, so only the caller that issued the read knows which list came back.

byte5 == len(frame) - 8 held for every frame recorded in this session.

The pump publishes its own setpoint ranges

Object 86, type 301 v1, three big-endian floats at offsets 0, 4 and 8 of the struct: default, minimum, maximum.

sub mode default min max native
13 constant speed 2800 1650 3671 RPM
15 constant pressure 1.632 1.000 2.450 Pa ÷ 9806.65
17 proportional pressure 3.649 2.599 4.569 Pa ÷ 9806.65
39 constant flow 0.228 0.114 2.498 m³/s × 3600

Every one of these contradicts the constants this client validated against (500–4500 RPM, 0.5–10 m, 0.5–10 m, 0.1–10 m³/h), in both directions and on every mode. Proportional pressure is the worst: a 0.5 m floor against a real one of 2.6 m, a range that does not even overlap constant pressure's.

A Class 10 reply carries a second acknowledgement

Confirmed by accident while probing the limiter objects. Reading a sub-id the pump does not implement returns

24 05 F8 E7 0A 01 04 EE 26

whose APDU head 0x01 is ack OK with one payload byte — and that byte is 0x04. That is the Class 10 status OPERATION_FAILED, from the decompiled GO app's GeniAPDU.CLASS10_ACK_* (0 OK, 2 BUSY, 4 OPERATION_FAILED). So the head ack alone is not the verdict: an unimplemented object answers "understood, and it failed".

The status byte must only be read at len >= 9. In an eight-byte frame declaring one payload byte, data[6] is the CRC's high byte.

The limiters: two of them, both disabled (ESPHome issue #274)

geni_profile_52_7.xml describes limiter_user_config (type 895, Obj 86 sub 600–619), limiter_factory_config (897, 620–639), limiter_status (896, 640–659) and limitation_manager_status (896, 660). The capture corpus stops at 86/601 and 86/621, so this could only be settled on hardware.

Sub-ids 602–619, 622–639 and 642–659 do not exist: every one answers OPERATION_FAILED. Only indices 1 and 2 are implemented, and the name enum at geni_profile_52_7.xml:1386 gives MaxFlow = 1, MinFlow = 2. So the instances are per limiter, not per mode.

user config 895, 18 bytes: [name][enable][limit f32 m³/s][kp][ti][td]
  600  01 00 38c676f1 3f19999a 3fcccccd 3ecccccd   MaxFlow disabled, 0.341 m³/h (1.50 gpm)
  601  02 00 3925631d 3f19999a 3fcccccd 3ecccccd   MinFlow disabled, 0.567 m³/h (2.50 gpm)

factory config 897, 9 bytes: [name][lower f32][upper f32]
  620  01 38044f4b 3a35ed8d    MaxFlow  0.114 - 2.498 m³/h
  621  02 38844f4b 3a5700d9    MinFlow  0.227 - 2.952 m³/h

status 896, 6 bytes: [name][limiting][reference f32]
  640  01 00 00000000    MaxFlow not limiting
  641  02 00 00000000    MinFlow not limiting
  660  00 00 00000000    manager not limiting

MaxFlow's factory bounds are exactly the constant-flow setpoint range read from 86/39, which is what makes the type-301 range the factory range: it does not account for a limiter that is enabled. On this unit neither is, so a setpoint here is delivered as written. On a unit with MaxFlow enabled it would not be, and nothing in the type-301 range would say so.

Class 10 SETs are acknowledged, in 90-120 ms

Measured through this client against an ALPHA HWR, capturing every inbound frame during a temperature-range write:

Object 86 Sub 10   +119.6 ms   24 05 F8 E7 0A 01 00 AE A2
Object 91 Sub 430  +119.8 ms   24 05 F8 E7 0A 01 00 AE A2
Object 84 Sub 1     +89.8 ms   24 05 F8 E7 0A 01 00 AE A2

Consistent with the capture corpus, which puts SET latency at 36-193 ms and nothing anywhere over 295 ms. SET_ACK_TIMEOUT = 0.4 clears all of it.

The acknowledgement is not the verdict. This pump clamps values it dislikes rather than refusing them, so only a readback says what was stored.

The measurement that said otherwise, and why it was wrong

An earlier entry here claimed the opposite - that a Class 10 SET draws no reply at all, and that the pump then answers nothing for 200-400 ms. Both came from a raw probe that wrote each GENI frame in a single write_gatt_char call, and this pump ignores a frame that is not split into 20-byte GATT writes, whatever the ATT MTU has been negotiated to.

The negotiated MTU on this link is 65, so 27 bytes fits comfortably at the ATT layer. It still does not work:

Object 84 Sub 1 SET, one 27-byte write   -> no reply
the same bytes, chunked at 20            -> acked in 111 ms
Object 84 Sub 1 GET, 11 bytes, one write -> answered in 69 ms

Reads are 11 bytes and fit, which is why every read in that probe worked and every write did not. The writes were never arriving, so nothing answered them, and the "deaf window" was the pump's own reassembly timer recovering from a truncated frame - the same mechanism as esphome-alpha-hwr #200, seen from the other side.

Two lessons worth keeping. A negative result from a hand-rolled probe is only as good as the probe: check it can do something you know works before believing what it says is impossible. And BLE_MTU_LIMIT = 20 in the transport is a pump requirement, not a guess about the radio.

An Object 91 Sub 430 write is visible ~450 ms after it is issued

Through the full write sequence — mode request, limits-tail read, Obj 91 SET, overview commit — polling the readback as fast as the link allows:

run target visible after
1 39.0 °C 449 ms
2 38.9 °C 459 ms
3 39.0 °C 486 ms
4 38.9 °C 456 ms

So the 1.2 s confirm delay is about 2.5× the settle time. Most of the 450 ms is the deaf window above: the commit is the last SET in the sequence, and the readback cannot be answered until the pump returns.

A consequence worth stating, because it removes a failure mode rather than adding one: reading too early does not return a stale value, it returns nothing. The confirm already retries an unanswered read.

The GO app sends consecutive SETs back to back

Recorded while chasing a window that turned out not to exist (above). It still says something true about pacing.

Consecutive SETs are not spaced. Across the corpus there are 289 consecutive SET-to-SET pairs:

min 43 ms   p50 62   p90 121
under 200 ms: 267 of 289

The tightest include 84/1000 -> 84/1001 at 43 ms - a schedule layer upload - and 86/10 -> 91/430 at 54 ms, the mode-request-then-write pair. Those uploads write five layers and then commit, and they work: if a SET inside the window were dropped, every upload would lose four of its five layers, and every single-event save would lose four of its five slots.

The app's 2500 ms pause is armed only before a non-SET. From DongleHelper.handleOutgoingQueue:

} else if (isSetOperation(t) && !isSetOperation(peekNextTelegramInQueue())) {
    this.noSentBefore = SystemClock.uptimeMillis() + getAfterSetPause();
} else {
    this.noSentBefore = 0L;
}

The else branch clears the pause outright, so consecutive writes are deliberately not spaced. The 2500 ms is a read guard, not a write guard.

GENIbus agrees. The Application Programming Manual promises a reply per request and says "the SET operation never returns anything but the APDU Head" - which is exactly the nine-byte frame measured above.

The raw Obj 91 write does not take on its own

Writing Object 91 Sub 430 directly — with a correct frame, a valid CRC, and the overview commit after it — leaves the stored value unchanged, whether the commit is sent 50 ms or 600 ms later (2 attempts each). The same value written through the client's sequence, which sends the Object 86 Sub 10 mode request first, takes every time.

So the mode request is not optional dressing around the temperature-range write; it is load-bearing. What exactly it enables was not established here — only that the write does not persist without it.

Frame-drop baseline: 23,579 frames, none dropped

Twenty-five minutes reading Object 84 Sub 1 as fast as the transport's pacing allows, 15.7 frames per second. Sustained polling is normal for this device - the GO app issues 2,516 GETs of Object 86 Sub 6 in the capture corpus.

duration        25.0 min
reads issued    23,579
unanswered      0
frames received 23,579
errors          0

crc_failures           0
stale_partials         0
unsolicited_fragments  0
runt_length_drops      0
overflow_drops         0
queue_full_drops       0

With zero events in 23,579 frames the 95% upper bound on the drop rate is 3/23,579 - better than one in 7,860. If the true rate were the one in 5,900 the ESPHome port saw, four drops would have been expected here and seeing none has probability 0.018.

Two things this does not say. The ESPHome figure counts one occurrence per 5,900 log lines, not per frame, so the two are not directly comparable and the comparison above is indicative rather than a contradiction. And this bounds this link - a macOS host a few metres from the pump - not an ESP32's. A radio result does not travel between radios.

What it does establish is that the frame path is clean enough that a timeout on this bench is not a silently corrupted frame, which is what the counters exist to tell you. An earlier version of this note recorded 167 frames, which could not distinguish zero from one in 5,900.

The pump keeps local wall clock, and has no idea UTC exists

This decides how every client must write the pump's clock, so it matters beyond this codebase: the GO app, the ESPHome component and this library all write the same register, and the pump cannot say which time base a value arrived in.

Read from the bench unit:

DateTimeActual  (94/101, type 322 v1)   07ea08140f221b0100040101
  year 2026  month 8  day 20  hour 15  min 34  sec 27
  day_w Thu   dst_status 1 = SummerTime
  -> 2026-08-20 15:34:27, against a host local clock of 15:34:28

DaylightSavingTime (94/102, type 323 v1)  01030702020b0701023c
  enabled                 1
  start  Mar, Sunday, occurrence 2, hour 2
  end    Nov, Sunday, occurrence 1, hour 2
  time_offset             60

Three things follow, and the third is the one that settles the timestamps:

  1. The clock is local. A device that reports whether it is currently in summer time is not keeping UTC.
  2. The pump applies DST itself - enabled, with the US rule and a 60-minute offset - so it shifts its own clock twice a year.
  3. There is no timezone or UTC-offset field anywhere in the GENI profile. Searching the whole of geni_profile_52_7.xml for timezone, UTC, GMT or offset returns only electrical offsets and alarm names. The pump therefore cannot convert between bases even in principle.

So a 32-bit timestamp the pump stores - ClockProgramSingleEvent's begin and end, the event log's entries, the cycle timestamps - must be in the same base as its clock, because the pump compares them against it and has no offset to relate the two. That base is local. The stored value is the local wall clock stamped as though it were UTC, which is what calendar.timegm on naive local fields produces.

This agrees with the earlier behavioural measurement, where an event written under this encoding started four seconds from its intended wall clock - and it explains why, rather than leaving it as a lucky guess.

What this client had wrong

set_clock and the single-event encoding were already right. The event log and the trend history decoded their timestamps with datetime.fromtimestamp(ts, tz=UTC), which produces the correct digits attached to the wrong instant: calling .astimezone() on one shifted it by the local offset. All four surfaces now go through alpha_hwr.pump_time.

A consequence worth knowing

Because the pump shifts its own clock at a DST transition, a stored event keeps its wall clock across the boundary - an 07:00 event stays at 07:00. That is almost certainly the intent, and it is another thing true-UTC storage would break.

The pump clamps a setpoint rather than refusing it

Measured through the client, constant speed, whose published range is 1650-3671 RPM:

4000 RPM -> clamped   stored 3671
2000 RPM -> accepted  stored 2000
 600 RPM -> clamped   stored 1650

Which reproduces the 0.7.0 note ("600 RPM is stored as 1650 and 4400 stores 3671") from a separate run, and settles how the client should behave: it does not pre-refuse a value outside the published range. The pump answers with what it stored, and that answer is more informative than a refusal.

There is a second reason it must not, raised by @jfriend00 on esphome-alpha-hwr #276 and worth recording here because it is not recoverable from the range alone. With a flow limiter enabled there is no maximum speed. The pump accepts a speed setpoint and then manages the actual run speed to hold the flow bound, and where it settles is a property of the installation's hydraulics rather than of the pump - on one reported loop a 3000 RPM request delivered 1885 RPM. No number is the bound there, so any check that looked authoritative would be wrong in a way the client cannot detect.

So the published range is an explanation, not a gate. It goes in the settle detail when the pump clamps, and only when it came from the pump:

4000 RPM -> clamped: pump stored 3671; its range for this mode is
                     1650-3671 RPM

The one thing still refused before the wire is a value that is not a number. There is nothing there for the pump to clamp to, and the all-ones float doubles as the SETPOINT_KEEP sentinel, so a NaN would read as "leave the setpoint alone" - a write that silently does nothing rather than one that fails.