Packet Trace: Alarms and Warnings

This document describes how to query and parse alarm/warning status from the ALPHA HWR pump.

Overview

The ALPHA HWR reports active alarms and warnings through Object 88 using the Active Query Response format. Unlike other telemetry that streams automatically via notifications, alarm/warning status must be queried explicitly.

Query Format

Alarms and warnings use the standard Class 10 READ operation (OpSpec 0x03):

[Start] [Length] [Src] [Dest] [Class] [OpSpec] [Reg-H] [Reg-M] [Reg-L] [CRC]

Query Alarms (Object 88, Sub 0)

Register address: 0x580000

27 07 E7 F8 0A 03 58 00 00 XX XX

Breakdown: - 27: Request start byte - 07: Length (7 bytes total) - E7: Source (Client) - F8: Destination (Pump) - 0A: Class 10 - 03: OpSpec (READ) - 58 00 00: Register (Obj=88, Sub=0 for alarms) - XX XX: CRC16

Query Warnings (Object 88, Sub 11)

Register address: 0x58000B

27 07 E7 F8 0A 03 58 00 0B XX XX

Breakdown: - Same as alarms query - 58 00 0B: Register (Obj=88, Sub=11 for warnings)

Response Format

The reply uses the standard response layout. Its byte 5 reads 0x09, which is the payload length — see below:

[Start] [Length] [Dest] [Src] [Class] [Byte5=len] [ID-A (2B)] [ID-B (2B)] [Data...] [CRC]

No Active Alarms Response

Validated on real hardware (ESPHome implementation):

24 0D F8 E7 0A 09 00 02 3A 01 00 00 02 00 00 DC 50

Breakdown: - 24: Response start byte - 0D: Length (13 bytes) - F8: Destination (Client) - E7: Source (Pump) - 0A: Class 10 - 09: payload length (9 bytes) - 00 02: Sequence number - 3A 01: ID field (depends on register queried) - 00 00: Reserved - 02: DataLen (2 bytes of data) - 00 00: Data (uint16 = 0x0000, meaning "no alarms") - DC 50: CRC16

Interpretation: The data value 0x0000 means there are no active alarms or warnings. This is the normal/healthy state.

Active Alarms Response

Constructed, not captured

The no-alarm response above is a real capture. This one is built by hand to show how multiple codes are laid out — a pump with two active alarms was not available to record. Its CRC is a placeholder and its length fields are illustrative. Trust the field layout, not the bytes.

Illustrative example, alarm codes 42 and 7:

24 11 F8 E7 0A 09 00 03 58 00 00 00 06 00 2A 00 07 00 00 XX XX

Breakdown: - 24: Response start byte - 11: Length (17 bytes) - F8: Destination (Client) - E7: Source (Pump) - 0A: Class 10 - 09: payload length (9 bytes) - 00 03: Sequence number - 58 00: ID field (Obj=88, Sub=0 for alarms) - 00 00: Reserved - 06: DataLen (6 bytes of data) - 00 2A: Alarm code 42 (uint16 big-endian) - 00 07: Alarm code 7 (uint16 big-endian) - 00 00: Terminating zero (filtered out) - XX XX: CRC — not computed for this constructed example - XX XX: CRC16

Interpretation: This packet indicates two active alarms with codes 42 and 7.

Active Warnings Response

Same format as alarms, but ID field reflects Object 88, Sub 11:

24 0F F8 E7 0A 09 00 04 58 0B 00 00 04 00 05 00 00 XX XX

Breakdown: - 58 0B: ID field (Obj=88, Sub=11 for warnings) - 04: DataLen (4 bytes) - 00 05: Warning code 5 - 00 00: Terminating zero (filtered out) - XX XX: CRC — not computed for this constructed example

Data Format

Payload Structure

The data section contains an array of uint16 values in big-endian format:

[Code1-H] [Code1-L] [Code2-H] [Code2-L] ... [0x00] [0x00]

Important Notes: - Each alarm/warning code is a 2-byte unsigned integer - Byte order is big-endian (high byte first) - A code value of 0x0000 means "no alarm/warning" - Zero codes should be filtered out when parsing - The array is typically terminated with a zero value

Example Parsing (Python)

import struct


def parse_alarm_response(packet: bytes) -> list[int]:
    """Parse alarm/warning codes from the alarm response."""
    if len(packet) < 13:
        return []

    # Extract data length at offset 12
    data_len = packet[12]

    # Parse uint16 array starting at offset 13
    codes = []
    offset = 13
    while offset + 2 <= len(packet) - 2 and offset < 13 + data_len:
        code = struct.unpack(">H", packet[offset : offset + 2])[0]
        if code != 0:  # Filter out zero codes
            codes.append(code)
        offset += 2

    return codes


# Example: No alarms
packet = bytes.fromhex("24 0D F8 E7 0A 09 00 02 3A 01 00 00 02 00 00 DC 50")
print(parse_alarm_response(packet))  # Output: []

# Example: Active alarms 42 and 7 - CONSTRUCTED, not captured.
# The final two bytes are placeholders; parse_alarm_response ignores them.
packet = bytes.fromhex(
    "24 11 F8 E7 0A 09 00 03 58 00 00 00 06 00 2A 00 07 00 00 00 00"
)
print(parse_alarm_response(packet))  # Output: [42, 7]

Byte 5 is a length, not an OpSpec

Earlier revisions of this page called 0x09 the "alarm/warning OpSpec" and listed 0x30, 0x2B and 0x14 alongside it as the motor-state, flow and temperature OpSpecs. Those are payload lengths — 9, 48, 43 and 20 bytes.

In a response, byte 5 is a length field. Measured across 13 objects and 10 distinct values:

0x09 = 0b00001001
       ││└─────┴─ Bits 0-5: payload length (9)
       └┴──────── Bits 6-7: operation code, always 00 in a response

and both of these hold without exception:

len(frame) == (frame[5] & 0x3F) + 8
frame[1]   == (frame[5] & 0x3F) + 4

This is not a naming quibble. Treating {0x30, 0x2B, 0x14, 0x2E, 0x2D, 0x09} as "the register-read operation specifiers" and filtering replies against it filtered by length — which is why the event log, whose entries carry a 20-byte payload, had to be exempted from the filter by hand.

Matching the reply

A reply is matched by the identifier pair at bytes 6-9, which names the object's type. See wire_format.md.

What distinguishes this response

Alarm and warning payloads are uint16 codes, not IEEE 754 floats. 0x0000 means none.

Integration Notes

Polling Frequency

Unlike streaming telemetry, alarms/warnings must be polled:

  • Recommended interval: 5-10 seconds
  • Minimum interval: 1 second (avoid overwhelming the pump)
  • On-demand: Query after pump mode changes or errors

Error Handling

  • If the pump doesn't respond, retry after 2-3 seconds
  • If you receive malformed data, log the raw packet hex for debugging
  • Empty response (DataLen=0) should be treated as "no data available"

Home Assistant Integration

Example ESPHome text sensor configuration:

text_sensor:
  - platform: ble_client
    name: "Active Alarms"
    id: active_alarms
    # Updated when alarm query response received

  - platform: ble_client
    name: "Active Warnings"
    id: active_warnings
    # Updated when warning query response received

Historical Context

Initial Confusion (Now Resolved)

Early Python implementations incorrectly expected OpSpec 0x13 for alarm responses. This was based on speculation before testing against actual hardware.

Testing confirmed the pump does answer, with a 9-byte payload in the standard response layout.

Discovery

Testing against real hardware revealed consistent 9-byte replies carrying 0x0000, which was initially misinterpreted as "not supported." In reality 0x0000 simply means "no active alarms."

References

Validation

This documentation is based on:

  • Real-world testing with an ALPHA HWR pump
  • Successful ESPHome C++ implementation (tested on ESP32-C3)
  • Cross-validation between Python and ESPHome implementations
  • Protocol documentation at https://eman.github.io/alpha-hwr/reimplementation/