A kWh in the battery is worth what the energy in the battery cost: the running average over everything it holds, solar at the export it gave up and grid energy at what it was bought for. A kWh drawn from it also pays the discharge's loss and wear. Where the sun will refill the room a draw frees, a kWh drawn costs no more than that sun.

The stored cost, v

The battery's energy came from somewhere, and it cost something to put there:

  • Solar cost the export the site gave up to store it, at the export price when it was charged.
  • Grid energy cost the import price it was bought at.

Charging one AC kWh at price p stores η_c kWh, so a stored kWh costs p / η_c. v is the average of that cost over all the battery holds, weighted by energy: the battery's pool, its stored kWh and what they cost together.

Why this, and not what will replace the kWh. A rule that prices a kWh by its replacement must decide where the replacement comes from: the grid tonight, or the sun tomorrow. That is a forecast about the plant's future, and it can be wrong both ways. What the energy in the battery cost is known. A kWh the battery delivers is that energy, so it costs what that energy cost.

How v moves

  • Charging adds to the pool at cost. A kWh of solar adds p_export / η_c, a kWh from the grid p_import / η_c, at the prices of the slot it charges in, where η_c is the stored kWh per kWh charged by the path that source takes, as the plant model answers it (Storage.stored_per_kwh). On a battery on its own inverter both cross the same conversion. On a hybrid's DC bus, DC-coupled PV reaches the battery's port as it is and pays only the port's conversion (none for a folded battery's meter factor aside), while the grid's AC crosses the hybrid first: a split battery stores less of a grid kWh than of a DC PV kWh.
  • Drawing takes energy at the average. A discharge lowers the pool's energy and its cost in proportion, so v stays where it was. Only charging moves it.
  • The meter wins. The pool is scaled to the stored energy the battery reports, at its own average, so energy the model cannot explain (self-discharge, meter timing) changes how much is held, not what it cost per kWh.

Why the average, and not the next lot drawn. The battery's lots say what the battery holds by source, and they must take each discharge from some lot first: the house from grid energy, exports from solar. That order is bookkeeping. The energy in a battery is all the same once stored; which lot a kWh "came from" is a convention, and a price that moved with it would move for no physical reason. The pool's average moves only when something charges the battery.

Energy of unknown origin

Some of what the battery holds may have no known cost: what it held when the ledger began, energy the meter finds when the model held none, or all of it when the client gives no lots. It is priced as bought, at the import price: the first slot's for what the ledger held when it began, that slot's for energy the meter finds, the valuation's first slot's when no lots are given.

The reason is the library's rule for anything it cannot vouch for: degrade conservatively. A low price is permission to run; a battery kWh priced as cheap solar that was in fact bought at the peak would send a load onto energy that cost the site dearly. Not knowing what the energy cost moves its price toward the import. Without lots the valuation also names battery_lots in degraded, and stays stored_value_v1: its values are already the conservative ones, so they stand.

It washes out as the battery cycles: once the battery has been through a discharge and a charge, the pool holds energy whose cost is known. A client gives the battery's lots from its ledger (Inputs).

Run forward along each scenario

v is not fixed over the horizon. For each PV scenario the pool is run forward along that scenario's projection: what the plant will charge, from where, at what price. A slot after an overnight grid top-up prices a battery that then holds that grid energy; a slot after a sunny morning, one that holds the morning's solar. So a later slot prices what the battery will hold then, under each scenario's weather.

The opportunity cost of a full battery

A battery full of grid energy that the price kept full would have nowhere to put the day's sun: the PV would be exported, or curtailed, while the battery held energy bought at the import price. Not discharging has a cost: the room it does not free.

So the price looks ahead with the make-up rule's events. Where the first event after the slot is a fill, the sun refills the room a draw frees before the battery needs the grid, and a kWh drawn now is replaced by solar that would otherwise have spilled. Then

v = min(stored cost, the fill's refill cost)

where the refill cost is the export the refilling PV gives up (0 where it would have been curtailed), plus its charge wear, per stored kWh. A battery filled from the grid overnight, with a sunny day ahead, is priced near the export price, and a scheduler draws it down. Where no fill comes first (a top-up, the battery running empty, the horizon), nothing refills the room for free, and the stored cost stands.

The dead band

Given v, a kWh taken from the battery's cycle costs one of two things, depending on where it comes from:

The kWh comes from It costs Why
PV that was charging the battery p_export now it is solar: a load that takes it gives up the export the site gave up to store it
the battery, discharging or able to v / η_d + c_dis the battery delivers a kWh more: it draws 1/η_d stored kWh at v each, and wears c_dis

Here η_c and η_d are the charge and discharge efficiencies, and c_dis the wear per AC kWh discharged, from the plant's battery settings. Each efficiency is the inverter's at the margin of the power it already converts in that slot: the loss grows with power, so a kWh more at 5 kW loses more than a kWh more at 0.5 kW. The charge's own wear is not in v: it was spent when the energy was stored. The inverter's fixed draws (standby, and its extra draw while the battery works) are the plant model's: a marginal kWh does not pay them.

One exception: where the grid is topping the battery up in the same slot, PV a load diverts from charging is replaced by the grid there and then, so it costs that import. That replacement is no forecast; it happens in the slot. The same holds for the grid's own charge diverted at an import limit.

Between the two lies the dead band: a battery kWh costs more than the solar that charged it, by the round trip's loss and the discharge's wear. A load gains nothing by taking energy through the battery that it could take from the sun directly.

The cases, with numbers

A battery with η_c = η_d = 0.95 and wear 0.02 per kWh each way (the charge's wear only enters a refill). Export 0.07, a night import of 0.18:

The battery holds v, per stored kWh A battery kWh costs
solar, charged at export 0.07 0.07 / 0.95 = 0.0737 0.0737 / 0.95 + 0.02 = 0.0976
grid energy, bought at 0.18 0.18 / 0.95 = 0.1895 0.1895 / 0.95 + 0.02 = 0.2194
half of each (0.0737 + 0.1895) / 2 = 0.1316 0.1316 / 0.95 + 0.02 = 0.1585
grid energy at 0.18, and the sun refills it first min(0.1895, (0.07 + 0.02) / 0.95) = 0.0947 0.0947 / 0.95 + 0.02 = 0.1197
energy of unknown origin, import now 0.18 as bought: 0.1895 0.2194

PV diverted from charging costs the export now, 0.07, in every case (outside a slot where the grid is topping the battery up).

Read the table this way:

  • A battery full of solar is cheap all evening. 0.0976 against an evening peak of, say, 0.45: the energy cost the export the site gave up, plus the trip through the battery. A load that runs on it pays that.
  • Grid energy costs what it was bought for, and the trip. 0.18 at night is 0.22 by the time it reaches the house. A battery kWh can cost more than importing would at some hours (a night import at 0.18), and the price says so.
  • A full battery with sun ahead is drawn down. The fill bounds the price at 0.1197, not 0.2194: a kWh kept would cost the site a kWh of the day's sun.

Run on the plant of the make-up rule's worked day, with a grid-charge window at 01:00-05:00 filling the battery from 10 % to full at 0.18: at 07:00 a kWh from the battery costs 0.2194 on a sunless day (it holds grid energy), and 0.1197 on a sunny one.

The minimum spread

The battery price is also the break-even of the energy it holds. A kWh charged at p_c is only worth discharging into a use worth more than

p_c / (η_c η_d) + c_dis

which is what a battery kWh costs. With the battery above, energy charged from the grid at 0.18 needs a use worth more than 0.2194; solar that would have exported at 0.07 needs more than 0.0976. A scheduler that runs a load where the price is lowest spends the battery's energy where it is worth the most.

The make-up alternative

engine/2's battery_value = "replacement" prices a battery kWh by what will replace it instead: the make-up rule's first event, carried through the battery's conversion. There v is

  • after a fill or a top-up at price p, what charging it again costs: v = (p + c_ch) / η_c;
  • after the battery runs empty, or at the horizon, what it would have saved the house: v = η_d × (p − c_dis);

and PV diverted costs η_c × v − c_ch, the battery charged a kWh less. With the battery above:

Make-up event Make-up price p v PV diverted costs A battery kWh costs
fill, spilling at export 0.07 0.07 0.0947 0.07 0.1197
grid top-up at 0.18 0.18 0.2105 0.18 0.2416
empty, cheapest import 0.30 0.30 0.2660 0.2327 0.30
empty, inside a 0.45 peak 0.45 0.4085 0.3681 0.45

It answers a different question: what the site will pay to put the kWh back, if the plant's future goes as projected. Choose it when that is the question your scheduler asks (Tune the engine).

Values by source

A slot's price is what serves the kWh in it. A scheduler with a choice may want the price of each source separately, and why it is what it is. Each slot gives:

  • pv_value: a PV kWh diverted to a flexible load, at the bottom of the dead band (the export price), with its routing, where that PV would otherwise have gone: export, curtail or battery. Its weight is the share of scenarios in which PV had spare to give.
  • battery_value: a battery kWh drawn for a flexible load, at the top of the dead band, with what displaces it: export (the battery would have filled and spilled, or an export run ends sooner) or later_import (a top-up, an import once it runs empty, or the horizon). displaces is the make-up rule's event, reported on either rule. Its weight is the share of scenarios in which the battery had a kWh to give.

Each is an expectation over the scenarios in which the source had energy to give, and None where it had none.

The supply stack

A price holds for a small load. A big one can take all the spilling PV and move on to the battery, then the grid. The supply stack (supply) says how much power each price holds for in the slot, in the order the plant serves a load:

  1. spill: PV exported or curtailed, at the export it would have earned (0 where curtailed);
  2. pv: PV charging the battery, diverted, at the bottom of the dead band;
  3. battery: discharge up to its limit and the energy above its reserve, at the top of the dead band;
  4. grid: without limit (kw null), at the import price.

The order is the plant's, not sorted by price: the battery's step can cost more than the grid's, when it holds energy bought dearer than the import now. Where the grid already serves the slot (the house importing, or the battery held or empty with no PV charging it), the grid is the only step.

The stack is the median PV case's; marginal_cost is the average over all the scenarios. So the first step's price and marginal_cost can differ. In the example dataset at 13:00 local on 2026-10-22 the stack reads 1.08 kW of PV charging the battery at 0.07, then up to 6 kW from the battery at 0.1365 (it holds the week's solar and the night's top-up), then the grid at 0.30; marginal_cost is 0.07. A 1 kW load runs on diverted PV; a 3 kW load pays partly at the battery's step. Use the prices in a scheduler prices a load across the stack.

Setting the parameters

The efficiencies and the loss growth come from plant/2; microgrid fit-battery fits them from your meters. The wear defaults to 0, which prices cycling as free; set it (Describe your plant).